100 Amp Wire Size Calculator
Find the correct wire gauge for 100 amp circuits using NEC ampacity tables, voltage drop, and conductor material.
What Wire Size Do You Need for 100 Amps?
A 100 amp circuit needs a conductor whose NEC ampacity is at least 100 A. Copper 3 AWG is rated 100 A at 75°C. Aluminum 1 AWG is also rated 100 A. Longer runs may need a larger gauge to keep voltage drop within 3%.
NEC Ampacity and Voltage Drop
Minimum wire size from ampacity:
$$\text{Required ampacity} \geq I_{\text{circuit}}$$When checking voltage drop on AC single-phase circuits:
$$V_{\text{drop}} = 2 \times I \times R \times L$$For three-phase AC:
$$V_{\text{drop}} = \sqrt{3} \times I \times R \times L$$Where \(I\) is current in amperes, \(R\) is resistance in ohms per 1000 ft, and \(L\) is one-way length in thousands of feet. NEC recommends keeping total feeder drop near 3% for branch circuits.
Related tools: Voltage Drop Calculator, 220V Wire Size Calculator, and 3 Phase Motor Amperage Calculator.
Frequently Asked Questions
What size wire for 100 amp service?
Copper 3 AWG or aluminum 1 AWG meets the 100 A ampacity rating at 75°C. Local code, continuous load rules, and voltage drop may require 2 AWG copper or larger.
Can I use 4 AWG for 100 amps?
4 AWG copper is rated 85 A and is undersized for a full 100 A load. Use 3 AWG copper or larger unless the load is below the conductor ampacity.
Why check voltage drop on a 100 amp circuit?
Even with correct ampacity, long feeders lose voltage. Motors and appliances at the end of the run may underperform if drop exceeds 3% to 5%.
Copper or aluminum for 100 amp?
Copper has higher ampacity per gauge and lower resistance. Aluminum needs a larger gauge but costs less. Both are common in service panels when sized to NEC tables.
Does three-phase change the wire size?
Ampacity is the same per conductor. Voltage drop uses a \(\sqrt{3}\) multiplier instead of 2, which can allow a smaller gauge on long three-phase runs.