100 Amp Wire Size Calculator

Find the correct wire gauge for 100 amp circuits using NEC ampacity tables, voltage drop, and conductor material.

O M T

What Wire Size Do You Need for 100 Amps?

A 100 amp circuit needs a conductor whose NEC ampacity is at least 100 A. Copper 3 AWG is rated 100 A at 75°C. Aluminum 1 AWG is also rated 100 A. Longer runs may need a larger gauge to keep voltage drop within 3%.

NEC Ampacity and Voltage Drop

Minimum wire size from ampacity:

$$\text{Required ampacity} \geq I_{\text{circuit}}$$

When checking voltage drop on AC single-phase circuits:

$$V_{\text{drop}} = 2 \times I \times R \times L$$

For three-phase AC:

$$V_{\text{drop}} = \sqrt{3} \times I \times R \times L$$

Where \(I\) is current in amperes, \(R\) is resistance in ohms per 1000 ft, and \(L\) is one-way length in thousands of feet. NEC recommends keeping total feeder drop near 3% for branch circuits.

Related tools: Voltage Drop Calculator, 220V Wire Size Calculator, and 3 Phase Motor Amperage Calculator.

Frequently Asked Questions

What size wire for 100 amp service?

Copper 3 AWG or aluminum 1 AWG meets the 100 A ampacity rating at 75°C. Local code, continuous load rules, and voltage drop may require 2 AWG copper or larger.

Can I use 4 AWG for 100 amps?

4 AWG copper is rated 85 A and is undersized for a full 100 A load. Use 3 AWG copper or larger unless the load is below the conductor ampacity.

Why check voltage drop on a 100 amp circuit?

Even with correct ampacity, long feeders lose voltage. Motors and appliances at the end of the run may underperform if drop exceeds 3% to 5%.

Copper or aluminum for 100 amp?

Copper has higher ampacity per gauge and lower resistance. Aluminum needs a larger gauge but costs less. Both are common in service panels when sized to NEC tables.

Does three-phase change the wire size?

Ampacity is the same per conductor. Voltage drop uses a \(\sqrt{3}\) multiplier instead of 2, which can allow a smaller gauge on long three-phase runs.